Single Core Insulated Copper Conductor(Unsheathed)Flexible Cables 1100 Voltage Grade For Industrial Application
Basic Code
Nominal Cross Sectional area of conductor Sq. MM
Number/Nom. Dia of cond. strands* MM
Thickness of Insulation (Nom)MM
Approx. Overall Diameter MM
Current Carrying Max Capacity Amps
Max. Conductor Resistance per K.M. at 200 C Amps
WHFFDN---B1070
70
360/0.5
1. 4
14.10
256
0.272
WHFFDN---B1095
95
475/0.5
1. 6
16.40
304
0.206
WHFFDN---B1120
120
608/0.5
1. 6
18.00
359
0.161
WHFFDN---B1150
150
750/0.5
1. 8
20.10
406
0.129
WHFFDN---B1185
185
925/0.5
2.0
22.30
466
0.106
WHFFDN---B1240
240
1221/0.5
2.2
25.20
550
0.0801
Note : Conductor as per class V. Supplied in 100 meter lengths as per IS:694 & in bigger packings on request.