Single Core Insulated Copper Conductor (Unsheathed)Cable for Fixed Wiring 1100 Voltage Grade
Basic Code
Nominal Cross Sectional area of conductor
Stranding No./Nom Dia of Cond.
Thickness of Insulation (Nom) Stands*
Approx. Overall Diameter
Conduit/Trunking
Unenclosed clipped directly to a surface or on cable trays
Max. Conductor Resistance per K.M. at 200C Amps
Sq. MM
MM
MM
MM
Amps
Amps
Ohms
WHFMDNA11X0
1.0
7/0.43
0.7
2.8
13
14
18.10
WHFMDNA11X5
1.5
7/0.52
0.7
3.1
16
19
12.10
WHFMDNA12X5
2.5
7/0.67
0.8
3.8
22
26
7.41
WHFMDNA14X0
4.0
7/0.85
0.8
4.30
29
35
4.61
WHFMDNA16X0
6.0
7/1.04
0.8
4.90
37
49
3.08
WHFMDNA1010
10
7/1.35
1.0
6.30
50
66
1.83
WHFMDNA1016
16
7/1.70
1.0
7.40
68
89
1.15
WHFMDNA1025
25
7/1.70
1.2
9.10
85
116
0.727
WHFMDNA1035
35
7/2.50
1.2
10.30
109
143
0.524
WHFMDNA1050
50
19/1.78
1.4
12.20
144
174
0.387
Note : 1-6 sq.mm in 90 mtrs. and 10-50 sq.mm. in 100 mtrs & in bigger packing on request Generally as per IS:694. Manufactured against customer's orders only for economical runs.
The number and diameter of conductor strands are for reference only. Conductor resistance as per IS:8130 is the governing criteria.
Construction
Conductor : Plain annealed copper conductor as per IS:8130 Insulation : Primary - Natural PVC Type A PVC Secondary - Skin colour coated PVC. Colour : Red/Yellow/Blue/Black/Green
(25 sq. mm & above are provided with unicolour Insulation only)